Whether you are in search of military and defense parts, aerospace parts, or other similar product solutions, Satellite To Submarine Parts is your one-stop shop. Thank you for your interest in part number W-C-375 11, a Federal Specifications item that is listed alongside the description “Circuit Breaker” and the NSN 5925012945707. To guarantee a swift procurement process for NSN part number W-C-375 11, be sure to request a quote by filling out and submitting the RFQ form below, and one of our experts will offer a customized solution for your comparisons in response.
Note : We Will Not Share Your Information To Any Third Parties.
We list everything with as much relevant information as possible to ensure that customers can swiftly identify and procure the exact products they need. For instance, while part number W-C-375 11 is manufactured by Federal Specifications, it is specifically done so under CAGE Code 81348, a unique identifier assigned to a particular facility by the DLA that supplies to various government or defense agencies. Additionally, using the first digits of the NSN 5925-01-294-5707, one can also determine that this part falls under FSC 5925 Circuit Breakers. Keeping this in mind, initiate the purchasing process today to see why so many customers depend on us for the NSN items they require.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-01-294-5707 Item PartTypeName: CIRCUIT BREAKER | 5925 | 012945707 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | A | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
WC375/11-012 | 5 | 2 | 2 |
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | RECTANGULAR DIMENSIONAL ENVELOPE |
ABHP | OVERALL LENGTH | 6.312 INCHES NOMINAL |
ABKW | OVERALL HEIGHT | 2.750 INCHES NOMINAL |
ABMK | OVERALL WIDTH | 4.156 INCHES NOMINAL |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.187 INCHES NOMINAL |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AKPX | POLE QUANTITY | 2 |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 UNTHREADED HOLE |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 80.0 AMPERES AC AND 80.0 AMPERES DC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC AND 125.0 DC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 7500.0 AC AND 5000.0 DC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | BETWEEN POLE ONE AND TWO |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 100.000 MINIMUM AT 200 PCT AND 190.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
CWJK | CASE MATERIAL | PLASTIC |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
TEST | TEST DATA DOCUMENT | 81348-W-C-375 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS,BROCHURES,ETC.,THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS,INDUSTRY DIRECTORIES,AND SIMILAR TRADE PUBLICATIONS,REFLECTING G |
TTQY | TERMINAL TYPE AND QUANTITY | 4 COMPRESSION |
ZZZK | SPECIFICATION/STANDARD DATA | 81348-W-C-375/11 GOVERNMENT SPECIFICATION |