Whether you are in search of military and defense parts, aerospace parts, or other similar product solutions, Satellite To Submarine Parts is your one-stop shop. Thank you for your interest in part number FAL36100, a Schneider Electric Gmbh item that is listed alongside the description “Circuit Breaker” and the NSN 5925008912391. To guarantee a swift procurement process for NSN part number FAL36100, be sure to request a quote by filling out and submitting the RFQ form below, and one of our experts will offer a customized solution for your comparisons in response.
Note : We Will Not Share Your Information To Any Third Parties.
We list everything with as much relevant information as possible to ensure that customers can swiftly identify and procure the exact products they need. For instance, while part number FAL36100 is manufactured by Schneider Electric Gmbh, it is specifically done so under CAGE Code 63637, a unique identifier assigned to a particular facility by the DLA that supplies to various government or defense agencies. Additionally, using the first digits of the NSN 5925-00-891-2391, one can also determine that this part falls under FSC 5925 Circuit Breakers. Keeping this in mind, initiate the purchasing process today to see why so many customers depend on us for the NSN items they require.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-891-2391 Item PartTypeName: CIRCUIT BREAKER | 5925 | 008912391 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | U | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
FAL36100 | 2 | 2 | 3 |
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 5.125 INCHES NOMINAL |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.500 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 5.125 INCHES NOMINAL |
AJEC | BOSS HEIGHT | 0.125 INCHES NOMINAL |
AKPX | POLE QUANTITY | 3 |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 100.0 AMPERES AC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 14000.0 AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 60.000 MINIMUM AT 200 PCT AND 200.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 40.0 DEG CELSIUS MAXIMUM ALL LOCATIONS |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
ADAQ | BODY LENGTH | 6.000 INCHES NOMINAL |
ADAT | BODY WIDTH | 4.469 INCHES NOMINAL |
ADAU | BODY HEIGHT | 3.156 INCHES NOMINAL |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.172 INCHES NOMINAL |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.500 INCHES NOMINAL |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT |
CWJK | CASE MATERIAL | PLASTIC |
TTQY | TERMINAL TYPE AND QUANTITY | 6 COMPRESSION |